UPS-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE,
    OBJECT-IDENTITY, Counter32, Gauge32, Integer32, mib-2
        FROM SNMPv2-SMI
    DisplayString, TimeStamp, TimeInterval, TestAndIncr,
      AutonomousType, TEXTUAL-CONVENTION
        FROM SNMPv2-TC
    MODULE-COMPLIANCE, OBJECT-GROUP
        FROM SNMPv2-CONF;


upsMIB MODULE-IDENTITY
    LAST-UPDATED "9402230000Z"
    ORGANIZATION "IETF UPS MIB Working Group"
    CONTACT-INFO
           "        Jeffrey D. Case

             Postal: SNMP Research, Incorporated
                     3001 Kimberlin Heights Road
                     Knoxville, TN  37920
                     US

                Tel: +1 615 573 1434
                Fax: +1 615 573 9197

             E-mail: case@snmp.com"
    DESCRIPTION
            "The MIB module to describe Uninterruptible Power
            Supplies."
    ::= { mib-2 33 }

PositiveInteger ::= TEXTUAL-CONVENTION
    DISPLAY-HINT "d"
    STATUS       current
    DESCRIPTION
            "This data type is a non-zero and non-negative value."
    SYNTAX       INTEGER (1..2147483647)

NonNegativeInteger ::= TEXTUAL-CONVENTION
    DISPLAY-HINT "d"
    STATUS       current
    DESCRIPTION
            "This data type is a non-negative value."
    SYNTAX       INTEGER (0..2147483647)
upsObjects            OBJECT IDENTIFIER ::= { upsMIB 1 }


--
-- The Device Identification group.
--      All objects in this group except for upsIdentName and
--      upsIdentAttachedDevices are set at device initialization
--      and remain static.
--

upsIdent              OBJECT IDENTIFIER ::= { upsObjects 1 }

upsIdentManufacturer OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..31))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The name of the UPS manufacturer."
    ::= { upsIdent 1 }

upsIdentModel OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The UPS Model designation."
    ::= { upsIdent 2 }

upsIdentUPSSoftwareVersion OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The UPS firmware/software version(s).  This variable
            may or may not have the same value as
            upsIdentAgentSoftwareVersion in some implementations."
    ::= { upsIdent 3 }

upsIdentAgentSoftwareVersion OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..63))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The UPS agent software version.  This variable may or
            may not have the same value as
            upsIdentUPSSoftwareVersion in some implementations."
    ::= { upsIdent 4 }

upsIdentName OBJECT-TYPE
    SYNTAX     DisplayString (SIZE(0..63))
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "A string identifying the UPS.  This object should be
            set by the administrator."
    ::= { upsIdent 5 }

upsIdentAttachedDevices OBJECT-TYPE
    SYNTAX     DisplayString (SIZE(0..63))
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "A string identifying the devices attached to the
            output(s) of the UPS.  This object should be set by
            the administrator."
    ::= { upsIdent 6 }


--
-- Battery Group
--

upsBattery            OBJECT IDENTIFIER ::= { upsObjects 2 }

upsBatteryStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        unknown(1),
        batteryNormal(2),
        batteryLow(3),
        batteryDepleted(4)
    }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The indication of the capacity remaining in the UPS
            system's batteries.   A value of batteryNormal
            indicates that the remaining run-time is greater than
            upsConfigLowBattTime.  A value of batteryLow indicates
            that the remaining battery run-time is less than or
            equal to upsConfigLowBattTime.  A value of
            batteryDepleted indicates that the UPS will be unable
            to sustain the present load when and if the utility
            power is lost (including the possibility that the
            utility power is currently absent and the UPS is
            unable to sustain the output)."
    ::= { upsBattery 1 }

upsSecondsOnBattery OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "seconds"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "If the unit is on battery power, the elapsed time
            since the UPS last switched to battery power, or the
            time since the network management subsystem was last
            restarted, whichever is less.  Zero shall be returned
            if the unit is not on battery power."
    ::= { upsBattery 2 }

upsEstimatedMinutesRemaining OBJECT-TYPE
    SYNTAX     PositiveInteger
    UNITS      "minutes"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "An estimate of the time to battery charge depletion
            under the present load conditions if the utility power
            is off and remains off, or if it were to be lost and
            remain off."
    ::= { upsBattery 3 }

upsEstimatedChargeRemaining OBJECT-TYPE
    SYNTAX     INTEGER (0..100)
    UNITS      "percent"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "An estimate of the battery charge remaining expressed
            as a percent of full charge."
    ::= { upsBattery 4 }

upsBatteryVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Volt DC"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the present battery voltage."
    ::= { upsBattery 5 }

upsBatteryCurrent OBJECT-TYPE
    SYNTAX     Integer32
    UNITS      "0.1 Amp DC"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present battery current."
    ::= { upsBattery 6 }

upsBatteryTemperature OBJECT-TYPE
    SYNTAX     Integer32
    UNITS      "degrees Centigrade"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The ambient temperature at or near the UPS Battery
            casing."
    ::= { upsBattery 7 }


--
-- Input Group
--

upsInput              OBJECT IDENTIFIER ::= { upsObjects 3 }

upsInputLineBads OBJECT-TYPE
    SYNTAX     Counter32
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "A count of the number of times the input entered an
            out-of-tolerance condition as defined by the
            manufacturer.  This count is incremented by one each
            time the input transitions from zero out-of-tolerance
            lines to one or more input lines out-of-tolerance."
    ::= { upsInput 1 }


upsInputNumLines OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The number of input lines utilized in this device.
            This variable indicates the number of rows in the
            input table."
    ::= { upsInput 2 }

upsInputTable OBJECT-TYPE
    SYNTAX     SEQUENCE OF UpsInputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "A list of input table entries.  The number of entries
            is given by the value of upsInputNumLines."
    ::= { upsInput 3 }

upsInputEntry OBJECT-TYPE
    SYNTAX     UpsInputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "An entry containing information applicable to a
            particular input line."
    INDEX { upsInputLineIndex }
    ::= { upsInputTable 1 }

UpsInputEntry ::= SEQUENCE {
    upsInputLineIndex   PositiveInteger,
    upsInputFrequency   NonNegativeInteger,
    upsInputVoltage     NonNegativeInteger,
    upsInputCurrent     NonNegativeInteger,
    upsInputTruePower   NonNegativeInteger
}

upsInputLineIndex OBJECT-TYPE
    SYNTAX     PositiveInteger
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "The input line identifier."
    ::= { upsInputEntry 1 }

upsInputFrequency OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present input frequency."
    ::= { upsInputEntry 2 }

upsInputVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the present input voltage."
    ::= { upsInputEntry 3 }

upsInputCurrent OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 RMS Amp"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the present input current."
    ::= { upsInputEntry 4 }

upsInputTruePower OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the present input true power."
    ::= { upsInputEntry 5 }


--
-- The Output group.
--

upsOutput             OBJECT IDENTIFIER ::= { upsObjects 4 }

upsOutputSource OBJECT-TYPE
    SYNTAX     INTEGER {
        other(1),
        none(2),
        normal(3),
        bypass(4),
        battery(5),
        booster(6),
        reducer(7)
    }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present source of output power.  The enumeration
            none(2) indicates that there is no source of output
            power (and therefore no output power), for example,
            the system has opened the output breaker."
    ::= { upsOutput 1 }

upsOutputFrequency OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present output frequency."
    ::= { upsOutput 2 }

upsOutputNumLines OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The number of output lines utilized in this device.
            This variable indicates the number of rows in the
            output table."
    ::= { upsOutput 3 }

upsOutputTable OBJECT-TYPE
    SYNTAX     SEQUENCE OF UpsOutputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "A list of output table entries.  The number of
            entries is given by the value of upsOutputNumLines."
    ::= { upsOutput 4 }

upsOutputEntry OBJECT-TYPE
    SYNTAX     UpsOutputEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "An entry containing information applicable to a
            particular output line."
    INDEX { upsOutputLineIndex }
    ::= { upsOutputTable 1 }

UpsOutputEntry ::= SEQUENCE {
    upsOutputLineIndex   PositiveInteger,
    upsOutputVoltage     NonNegativeInteger,
    upsOutputCurrent     NonNegativeInteger,
    upsOutputPower       NonNegativeInteger,
    upsOutputPercentLoad INTEGER
}

upsOutputLineIndex OBJECT-TYPE
    SYNTAX     PositiveInteger
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "The output line identifier."
    ::= { upsOutputEntry 1 }

upsOutputVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present output voltage."
    ::= { upsOutputEntry 2 }

upsOutputCurrent OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 RMS Amp"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present output current."
    ::= { upsOutputEntry 3 }

upsOutputPower OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present output true power."
    ::= { upsOutputEntry 4 }

upsOutputPercentLoad OBJECT-TYPE
    SYNTAX     INTEGER (0..200)
    UNITS      "percent"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The percentage of the UPS power capacity presently
            being used on this output line, i.e., the greater of
            the percent load of true power capacity and the
            percent load of VA."
    ::= { upsOutputEntry 5 }

--
-- The Bypass group.
--

upsBypass             OBJECT IDENTIFIER ::= { upsObjects 5 }

upsBypassFrequency OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present bypass frequency."
    ::= { upsBypass 1 }

upsBypassNumLines OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The number of bypass lines utilized in this device.
            This entry indicates the number of rows in the bypass
            table."
    ::= { upsBypass 2 }

upsBypassTable OBJECT-TYPE
    SYNTAX     SEQUENCE OF UpsBypassEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "A list of bypass table entries.  The number of
            entries is given by the value of upsBypassNumLines."
    ::= { upsBypass 3 }

upsBypassEntry OBJECT-TYPE
    SYNTAX     UpsBypassEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "An entry containing information applicable to a
            particular bypass input."
    INDEX { upsBypassLineIndex }
    ::= { upsBypassTable 1 }

UpsBypassEntry ::= SEQUENCE {
    upsBypassLineIndex  PositiveInteger,
    upsBypassVoltage    NonNegativeInteger,
    upsBypassCurrent    NonNegativeInteger,
    upsBypassPower      NonNegativeInteger
}

upsBypassLineIndex OBJECT-TYPE
    SYNTAX     PositiveInteger
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "The bypass line identifier."
    ::= { upsBypassEntry 1 }

upsBypassVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present bypass voltage."
    ::= { upsBypassEntry 2 }

upsBypassCurrent OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 RMS Amp"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present bypass current."
    ::= { upsBypassEntry 3 }

upsBypassPower OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present true power conveyed by the bypass."
    ::= { upsBypassEntry 4 }


--
-- The Alarm group.
--

upsAlarm              OBJECT IDENTIFIER ::= { upsObjects 6 }

upsAlarmsPresent OBJECT-TYPE
    SYNTAX     Gauge32
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The present number of active alarm conditions."
    ::= { upsAlarm 1 }

upsAlarmTable OBJECT-TYPE
    SYNTAX     SEQUENCE OF UpsAlarmEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "A list of alarm table entries.  The table contains
            zero, one, or many rows at any moment, depending upon
            the number of alarm conditions in effect.  The table
            is initially empty at agent startup.  The agent
            creates a row in the table each time a condition is
            detected and deletes that row when that condition no
            longer pertains.  The agent creates the first row with
            upsAlarmId equal to 1, and increments the value of
            upsAlarmId each time a new row is created, wrapping to
            the first free value greater than or equal to 1 when
            the maximum value of upsAlarmId would otherwise be
            exceeded.  Consequently, after multiple operations,
            the table may become sparse, e.g., containing entries
            for rows 95, 100, 101, and 203 and the entries should
            not be assumed to be in chronological order because
            upsAlarmId might have wrapped.

            Alarms are named by an AutonomousType (OBJECT
            IDENTIFIER), upsAlarmDescr, to allow a single table to
            reflect well known alarms plus alarms defined by a
            particular implementation, i.e., as documented in the
            private enterprise MIB definition for the device.  No
            two rows will have the same value of upsAlarmDescr,
            since alarms define conditions.  In order to meet this
            requirement, care should be taken in the definition of
            alarm conditions to insure that a system cannot enter
            the same condition multiple times simultaneously.

            The number of rows in the table at any given time is
            reflected by the value of upsAlarmsPresent."
    ::= { upsAlarm 2 }

upsAlarmEntry OBJECT-TYPE
    SYNTAX     UpsAlarmEntry
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "An entry containing information applicable to a
            particular alarm."
    INDEX { upsAlarmId }
    ::= { upsAlarmTable 1 }

UpsAlarmEntry ::= SEQUENCE {
    upsAlarmId          PositiveInteger,
    upsAlarmDescr       AutonomousType,
    upsAlarmTime        TimeStamp
}

upsAlarmId OBJECT-TYPE
    SYNTAX     PositiveInteger
    MAX-ACCESS not-accessible
    STATUS     current
    DESCRIPTION
            "A unique identifier for an alarm condition.  This
            value must remain constant."
    ::= { upsAlarmEntry 1 }

upsAlarmDescr OBJECT-TYPE
    SYNTAX     AutonomousType
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "A reference to an alarm description object.  The
            object referenced should not be accessible, but rather
            be used to provide a unique description of the alarm
            condition."
    ::= { upsAlarmEntry 2 }

upsAlarmTime OBJECT-TYPE
    SYNTAX     TimeStamp
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The value of sysUpTime when the alarm condition was
            detected.  If the alarm condition was detected at the
            time of agent startup and presumably existed before
            agent startup, the value of upsAlarmTime shall equal
            0."
    ::= { upsAlarmEntry 3 }


--
-- Well known alarm conditions.
--

upsWellKnownAlarms    OBJECT IDENTIFIER ::= { upsAlarm 3 }

upsAlarmBatteryBad OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "One or more batteries have been determined to require
            replacement."
    ::= { upsWellKnownAlarms  1 }

upsAlarmOnBattery OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS is drawing power from the batteries."
    ::= { upsWellKnownAlarms  2 }

upsAlarmLowBattery OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The remaining battery run-time is less than or equal
            to upsConfigLowBattTime."
    ::= { upsWellKnownAlarms  3 }


upsAlarmDepletedBattery OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS will be unable to sustain the present load
            when and if the utility power is lost."
    ::= { upsWellKnownAlarms  4 }

upsAlarmTempBad OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A temperature is out of tolerance."
    ::= { upsWellKnownAlarms  5 }

upsAlarmInputBad OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "An input condition is out of tolerance."
    ::= { upsWellKnownAlarms  6 }

upsAlarmOutputBad OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "An output condition (other than OutputOverload) is
            out of tolerance."
    ::= { upsWellKnownAlarms  7 }

upsAlarmOutputOverload OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The output load exceeds the UPS output capacity."
    ::= { upsWellKnownAlarms  8 }

upsAlarmOnBypass OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The Bypass is presently engaged on the UPS."
    ::= { upsWellKnownAlarms  9 }

upsAlarmBypassBad OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The Bypass is out of tolerance."
    ::= { upsWellKnownAlarms 10 }

upsAlarmOutputOffAsRequested OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS has shutdown as requested, i.e., the output
            is off."
    ::= { upsWellKnownAlarms 11 }

upsAlarmUpsOffAsRequested OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The entire UPS has shutdown as commanded."
    ::= { upsWellKnownAlarms 12 }

upsAlarmChargerFailed OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "An uncorrected problem has been detected within the
            UPS charger subsystem."
    ::= { upsWellKnownAlarms 13 }

upsAlarmUpsOutputOff OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The output of the UPS is in the off state."
    ::= { upsWellKnownAlarms 14 }

upsAlarmUpsSystemOff OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS system is in the off state."
    ::= { upsWellKnownAlarms 15 }

upsAlarmFanFailure OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The failure of one or more fans in the UPS has been
            detected."
    ::= { upsWellKnownAlarms 16 }

upsAlarmFuseFailure OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The failure of one or more fuses has been detected."
    ::= { upsWellKnownAlarms 17 }

upsAlarmGeneralFault OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A general fault in the UPS has been detected."
    ::= { upsWellKnownAlarms 18 }

upsAlarmDiagnosticTestFailed OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The result of the last diagnostic test indicates a
            failure."
    ::= { upsWellKnownAlarms 19 }

upsAlarmCommunicationsLost OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A problem has been encountered in the communications
            between the agent and the UPS."
    ::= { upsWellKnownAlarms 20 }

upsAlarmAwaitingPower OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS output is off and the UPS is awaiting the
            return of input power."
    ::= { upsWellKnownAlarms 21 }

upsAlarmShutdownPending OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A upsShutdownAfterDelay countdown is underway."
    ::= { upsWellKnownAlarms 22 }

upsAlarmShutdownImminent OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The UPS will turn off power to the load in less than
            5 seconds; this may be either a timed shutdown or a
            low battery shutdown."
    ::= { upsWellKnownAlarms 23 }

upsAlarmTestInProgress OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A test is in progress, as initiated and indicated by
            the Test Group.  Tests initiated via other
            implementation-specific mechanisms can indicate the
            presence of the testing in the alarm table, if
            desired, via a OBJECT-IDENTITY macro in the MIB
            document specific to that implementation and are
            outside the scope of this OBJECT-IDENTITY."
    ::= { upsWellKnownAlarms 24 }


--
-- The Test Group
--

upsTest               OBJECT IDENTIFIER ::= { upsObjects 7 }

upsTestId OBJECT-TYPE
    SYNTAX     OBJECT IDENTIFIER
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The test is named by an OBJECT IDENTIFIER which
            allows a standard mechanism for the initiation of
            tests, including the well known tests identified in
            this document as well as those introduced by a
            particular implementation, i.e., as documented in the
            private enterprise MIB definition for the device.

            Setting this variable initiates the named test. Sets
            to this variable require the presence of
            upsTestSpinLock in the same SNMP message.

            The set request will be rejected with an appropriate
            error message if the requested test cannot be
            performed, including attempts to start a test when
            another test is already in progress.  The status of
            the current or last test is maintained in
            upsTestResultsSummary. Tests in progress may be
            aborted by setting the upsTestId variable to
            upsTestAbortTestInProgress.

            Read operations return the value of the name of the
            test in progress if a test is in progress or the name
            of the last test performed if no test is in progress,
            unless no test has been run, in which case the well
            known value upsTestNoTestsInitiated is returned."
    ::= { upsTest 1 }

-- see [6] for more information on the semantics of objects with
-- syntax of TestAndIncr

upsTestSpinLock OBJECT-TYPE
    SYNTAX     TestAndIncr
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "A spin lock on the test subsystem.  The spinlock is
            used as follows.

            Before starting a test, a manager-station should make
            sure that a test is not in progress as follows:

                try_again:
                  get (upsTestSpinLock)
                  while (upsTestResultsSummary == inProgress) {
                    /* loop while a test is running for another
            manager */
                    short delay
                    get (upsTestSpinLock)
                  }
                  lock_value = upsTestSpinLock
                  /* no test in progress, start the test */
                  set (upsTestSpinLock = lock_value, upsTestId =
            requested_test)
                  if (error_index == 1) { /* (upsTestSpinLock
            failed) */
                    /* if problem is not access control, then
                        some other manager slipped in ahead of us
            */
                    goto try_again
                  }
                  if (error_index == 2) { /* (upsTestId) */
                    /* cannot perform the test */
                    give up
                  }
                  /* test started ok */
                  /* wait for test completion by polling
            upsTestResultsSummary */
                  get (upsTestSpinLock, upsTestResultsSummary,
            upsTestResultsDetail)
                  while (upsTestResultsSummary == inProgress) {
                    short delay
                    get (upsTestSpinLock, upsTestResultsSummary,
            upsTestResultsDetail)
                  }
                  /* when test completes, retrieve any additional
            test results */
                  /* if upsTestSpinLock == lock_value + 1, then
            these are our test */
                  /* results (as opposed to another manager's */
                  The initial value of upsTestSpinLock at agent
            initialization shall
                  be 1."
    ::= { upsTest 2 }

upsTestResultsSummary OBJECT-TYPE
    SYNTAX     INTEGER {
        donePass(1),
        doneWarning(2),
        doneError(3),
        aborted(4),
        inProgress(5),
        noTestsInitiated(6)
    }
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The results of the current or last UPS diagnostics
            test performed.  The values for donePass(1),
            doneWarning(2), and doneError(3) indicate that the
            test completed either successfully, with a warning, or
            with an error, respectively.  The value aborted(4) is
            returned for tests which are aborted by setting the
            value of upsTestId to upsTestAbortTestInProgress.
            Tests which have not yet concluded are indicated by
            inProgress(5).  The value noTestsInitiated(6)
            indicates that no previous test results are available,
            such as is the case when no tests have been run since
            the last reinitialization of the network management
            subsystem and the system has no provision for non-
            volatile storage of test results."
    ::= { upsTest 3 }

upsTestResultsDetail OBJECT-TYPE
    SYNTAX     DisplayString (SIZE (0..255))
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "Additional information about upsTestResultsSummary.
            If no additional information available, a zero length
            string is returned."
    ::= { upsTest 4 }

upsTestStartTime OBJECT-TYPE
    SYNTAX     TimeStamp
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The value of sysUpTime at the time the test in
            progress was initiated, or, if no test is in progress,
            the time the previous test was initiated.  If the
            value of upsTestResultsSummary is noTestsInitiated(6),
            upsTestStartTime has the value 0."
    ::= { upsTest 5 }

upsTestElapsedTime OBJECT-TYPE
    SYNTAX     TimeInterval
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The amount of time, in TimeTicks, since the test in
            progress was initiated, or, if no test is in progress,
            the previous test took to complete.  If the value of
            upsTestResultsSummary is noTestsInitiated(6),
            upsTestElapsedTime has the value 0."
    ::= { upsTest 6 }

--
-- Well known tests.
--

upsWellKnownTests     OBJECT IDENTIFIER ::= { upsTest 7 }


upsTestNoTestsInitiated OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "No tests have been initiated and no test is in
            progress."
    ::= { upsWellKnownTests  1 }

upsTestAbortTestInProgress OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The test in progress is to be aborted / the test in
            progress was aborted."
    ::= { upsWellKnownTests  2 }

upsTestGeneralSystemsTest OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The manufacturer's standard test of UPS device
            systems."
    ::= { upsWellKnownTests  3 }

upsTestQuickBatteryTest OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "A test that is sufficient to determine if the battery
            needs replacement."
    ::= { upsWellKnownTests  4 }

upsTestDeepBatteryCalibration OBJECT-IDENTITY
    STATUS     current
    DESCRIPTION
            "The system is placed on battery to a discharge level,
            set by the manufacturer, sufficient to determine
            battery replacement and battery run-time with a high
            degree of confidence.  WARNING:  this test will leave
            the battery in a low charge state and will require
            time for recharging to a level sufficient to provide
            normal battery duration for the protected load."
    ::= { upsWellKnownTests  5 }


--
-- The Control group.
--

upsControl            OBJECT IDENTIFIER ::= { upsObjects 8 }

upsShutdownType OBJECT-TYPE
    SYNTAX     INTEGER {
        output(1),
        system(2)
    }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "This object determines the nature of the action to be
            taken at the time when the countdown of the
            upsShutdownAfterDelay and upsRebootWithDuration
            objects reaches zero.

            Setting this object to output(1) indicates that
            shutdown requests should cause only the output of the
            UPS to turn off.  Setting this object to system(2)
            indicates that shutdown requests will cause the entire
            UPS system to turn off."
    ::= { upsControl 1 }

upsShutdownAfterDelay OBJECT-TYPE
    SYNTAX     INTEGER (-1..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "Setting this object will shutdown (i.e., turn off)
            either the UPS output or the UPS system (as determined
            by the value of upsShutdownType at the time of
            shutdown) after the indicated number of seconds, or
            less if the UPS batteries become depleted. Setting
            this object to 0 will cause the shutdown to occur
            immediately.  Setting this object to -1 will abort the
            countdown.  If the system is already in the desired
            state at the time the countdown reaches 0, then
            nothing will happen.  That is, there is no additional
            action at that time if upsShutdownType = system and
            the system is already off.  Similarly, there is no
            additional action at that time if upsShutdownType =
            output and the output is already off.  When read,
            upsShutdownAfterDelay will return the number of
            seconds remaining until shutdown, or -1 if no shutdown
            countdown is in effect.  On some systems, if the agent
            is restarted while a shutdown countdown is in effect,
            the countdown may be aborted.  Sets to this object
            override any upsShutdownAfterDelay already in effect."
    ::= { upsControl 2 }

upsStartupAfterDelay OBJECT-TYPE
    SYNTAX     INTEGER (-1..2147483647)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "Setting this object will start the output after the
            indicated number of seconds, including starting the
            UPS, if necessary.  Setting this object to 0 will
            cause the startup to occur immediately.  Setting this
            object to -1 will abort the countdown.  If the output
            is already on at the time the countdown reaches 0,
            then nothing will happen.  Sets to this object
            override the effect of any upsStartupAfterDelay
            countdown or upsRebootWithDuration countdown in
            progress.  When read, upsStartupAfterDelay will return
            the number of seconds until startup, or -1 if no
            startup countdown is in effect.  If the countdown
            expires during a utility failure, the startup shall
            not occur until the utility power is restored.  On
            some systems, if the agent is restarted while a
            startup countdown is in effect, the countdown is
            aborted."
    ::= { upsControl 3 }

upsRebootWithDuration OBJECT-TYPE
    SYNTAX     INTEGER (-1..300)
    UNITS      "seconds"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "Setting this object will immediately shutdown (i.e.,
            turn off) either the UPS output or the UPS system (as
            determined by the value of upsShutdownType at the time
            of shutdown) for a period equal to the indicated
            number of seconds, after which time the output will be
            started, including starting the UPS, if necessary.  If
            the number of seconds required to perform the request
            is greater than the requested duration, then the
            requested shutdown and startup cycle shall be
            performed in the minimum time possible, but in no case
            shall this require more than the requested duration
            plus 60 seconds.  When read, upsRebootWithDuration
            shall return the number of seconds remaining in the
            countdown, or -1 if no countdown is in progress.  If
            the startup should occur during a utility failure, the
            startup shall not occur until the utility power is
            restored."
    ::= { upsControl 4 }

upsAutoRestart OBJECT-TYPE
    SYNTAX     INTEGER {
        on(1),
        off(2)
    }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "Setting this object to 'on' will cause the UPS system
            to restart after a shutdown if the shutdown occurred
            during a power loss as a result of either a
            upsShutdownAfterDelay or an internal battery depleted
            condition.  Setting this object to 'off' will prevent
            the UPS system from restarting after a shutdown until
            an operator manually or remotely explicitly restarts
            it.  If the UPS is in a startup or reboot countdown,
            then the UPS will not restart until that delay has
            been satisfied."
    ::= { upsControl 5 }


--
-- The Configuration group.
--

upsConfig             OBJECT IDENTIFIER ::= { upsObjects 9 }

upsConfigInputVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The magnitude of the nominal input voltage.  On those
            systems which support read-write access to this
            object, if there is an attempt to set this variable to
            a value that is not supported, the request must be
            rejected and the agent shall respond with an
            appropriate error message, i.e., badValue for SNMPv1,
            or inconsistentValue for SNMPv2."
    ::= { upsConfig 1 }

upsConfigInputFreq OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The nominal input frequency.  On those systems which
            support read-write access to this object, if there is
            an attempt to set this variable to a value that is not
            supported, the request must be rejected and the agent
            shall respond with an appropriate error message, i.e.,
            badValue for SNMPv1, or inconsistentValue for SNMPv2."
    ::= { upsConfig 2 }

upsConfigOutputVoltage OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The magnitude of the nominal output voltage.  On
            those systems which support read-write access to this
            object, if there is an attempt to set this variable to
            a value that is not supported, the request must be
            rejected and the agent shall respond with an
            appropriate error message, i.e., badValue for SNMPv1,
            or inconsistentValue for SNMPv2."
    ::= { upsConfig 3 }

upsConfigOutputFreq OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "0.1 Hertz"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The nominal output frequency.  On those systems which
            support read-write access to this object, if there is
            an attempt to set this variable to a value that is not
            supported, the request must be rejected and the agent
            shall respond with an appropriate error message, i.e.,
            badValue for SNMPv1, or inconsistentValue for SNMPv2."
    ::= { upsConfig 4 }

upsConfigOutputVA OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "Volt-Amps"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the nominal Volt-Amp rating."
    ::= { upsConfig 5 }

upsConfigOutputPower OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "Watts"
    MAX-ACCESS read-only
    STATUS     current
    DESCRIPTION
            "The magnitude of the nominal true power rating."
    ::= { upsConfig 6 }

upsConfigLowBattTime OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "minutes"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The value of upsEstimatedMinutesRemaining at which a
            lowBattery condition is declared.  For agents which
            support only discrete (discontinuous) values, then the
            agent shall round up to the next supported value.  If
            the requested value is larger than the largest
            supported value, then the largest supported value
            shall be selected."
    ::= { upsConfig 7 }

upsConfigAudibleStatus OBJECT-TYPE
    SYNTAX     INTEGER {
        disabled(1),
        enabled(2),
        muted(3)
    }
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The requested state of the audible alarm.  When in
            the disabled state, the audible alarm should never
            sound.  The enabled state is self-describing.  Setting
            this object to muted(3) when the audible alarm is
            sounding shall temporarily silence the alarm.  It will
            remain muted until it would normally stop sounding and
            the value returned for read operations during this
            period shall equal muted(3).  At the end of this
            period, the value shall revert to enabled(2).  Writes
            of the value muted(3) when the audible alarm is not
            sounding shall be accepted but otherwise shall have no
            effect."
    ::= { upsConfig 8 }

upsConfigLowVoltageTransferPoint OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The minimum input line voltage allowed before the UPS
            system transfers to battery backup."
    ::= { upsConfig 9 }

upsConfigHighVoltageTransferPoint OBJECT-TYPE
    SYNTAX     NonNegativeInteger
    UNITS      "RMS Volts"
    MAX-ACCESS read-write
    STATUS     current
    DESCRIPTION
            "The maximum line voltage allowed before the UPS
            system transfers to battery backup."
    ::= { upsConfig 10 }


--
-- notifications, i.e., traps
--
upsTraps              OBJECT IDENTIFIER ::= { upsMIB 2 }

-- This section defines the well-known notifications sent by
-- UPS agents.
-- Care must be taken to insure that no particular notification
-- is sent to a single receiving entity more often than once
-- every five seconds.

upsTrapOnBattery NOTIFICATION-TYPE
    OBJECTS { upsEstimatedMinutesRemaining, upsSecondsOnBattery,
              upsConfigLowBattTime }
    STATUS  current
    DESCRIPTION
            "The UPS is operating on battery power.  This trap is
            persistent and is resent at one minute intervals until
            the UPS either turns off or is no longer running on
            battery."
  ::= { upsTraps 1 }

upsTrapTestCompleted NOTIFICATION-TYPE
    OBJECTS { upsTestId, upsTestSpinLock,
              upsTestResultsSummary, upsTestResultsDetail,
              upsTestStartTime, upsTestElapsedTime }
    STATUS  current
    DESCRIPTION
            "This trap is sent upon completion of a UPS diagnostic
            test."
  ::= { upsTraps 2 }

upsTrapAlarmEntryAdded NOTIFICATION-TYPE
    OBJECTS { upsAlarmId, upsAlarmDescr }
    STATUS  current
    DESCRIPTION
            "This trap is sent each time an alarm is inserted into
            to the alarm table.  It is sent on the insertion of
            all alarms except for upsAlarmOnBattery and
            upsAlarmTestInProgress."
  ::= { upsTraps 3 }

upsTrapAlarmEntryRemoved NOTIFICATION-TYPE
    OBJECTS { upsAlarmId, upsAlarmDescr }
    STATUS  current
    DESCRIPTION
            "This trap is sent each time an alarm is removed from
            the alarm table.  It is sent on the removal of all
            alarms except for upsAlarmTestInProgress."
  ::= { upsTraps 4 }


--
-- conformance information
--
upsConformance        OBJECT IDENTIFIER ::= { upsMIB 3 }

upsCompliances        OBJECT IDENTIFIER ::= { upsConformance 1 }


--
-- compliance statements
--

upsSubsetCompliance MODULE-COMPLIANCE
    STATUS     current
    DESCRIPTION

            "The compliance statement for UPSs that only support
            the two-contact communication protocol."
    MODULE -- this module
        MANDATORY-GROUPS  { upsSubsetIdentGroup,
                  upsSubsetBatteryGroup, upsSubsetInputGroup,
                  upsSubsetOutputGroup, upsSubsetAlarmGroup,
                  upsSubsetControlGroup, upsSubsetConfigGroup }

    OBJECT     upsBatteryStatus
    SYNTAX     INTEGER {
        batteryNormal(2),
        batteryLow(3)
    }
    DESCRIPTION
            "Support of the values unknown(1) and
            batteryDepleted(4) is not required."

    OBJECT     upsAlarmDescr
    DESCRIPTION
            "Support of all `well known' alarm types is not
            required.  The well known alarm types which must be
            supported are: upsAlarmOnBattery, upsAlarmLowBattery,
            upsAlarmInputBad, upsAlarmUpsOutputOff,
            upsAlarmUpsSystemOff, and upsAlarmTestInProgress."

    OBJECT     upsOutputSource
    SYNTAX     INTEGER {
        normal(2),
        battery(4)
    }
    DESCRIPTION
            "Support of the values other(1), none(2), bypass(4),
            booster(6) and reducer(7) is not required."

    OBJECT     upsShutdownType
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one shutdown type."

    OBJECT     upsAutoRestart
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one restart type."

    OBJECT     upsConfigInputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigInputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."
    ::= { upsCompliances 1 }

upsBasicCompliance MODULE-COMPLIANCE
    STATUS     current
    DESCRIPTION

            "The compliance statement for UPSs that support
            full-featured functions, such as control."
    MODULE -- this module
        MANDATORY-GROUPS { upsBasicIdentGroup,
                  upsBasicBatteryGroup, upsBasicInputGroup,
                  upsBasicOutputGroup, upsBasicAlarmGroup,
                  upsBasicTestGroup, upsBasicControlGroup,
                  upsBasicConfigGroup }


    OBJECT     upsAlarmDescr
    DESCRIPTION
            "Support of all `well known' alarm types is not
            required.  The well known alarm types which must be
            supported are: upsAlarmOnBattery, upsAlarmLowBattery,
            upsAlarmDepletedBattery, upsAlarmTempBad,
            upsAlarmInputBad, upsAlarmOutputOverload,
            upsAlarmOnBypass, upsAlarmBypassBad,
            upsAlarmOutputOffAsRequested,
            upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
            upsAlarmUpsSystemOff, upsAlarmGeneralFault,
            upsAlarmDiagnosticTestFailed,
            upsAlarmCommunicationsLost, upsAlarmShutdownPending,
            and upsAlarmTestInProgress."

    OBJECT     upsTestId
    DESCRIPTION
            "Support of all `well known' test types is not
            required.  If no tests are supported, then the only
            well known test type which must be supported is
            upsTestNoTestsInitiated."

    OBJECT     upsOutputSource
    SYNTAX     INTEGER {
        normal(2),
        battery(4)
    }
    DESCRIPTION
            "Support of the values other(1), none(2), bypass(4),
            booster(6) and reducer(7) is not required."

        GROUP upsBasicBypassGroup
        DESCRIPTION
            "The upsBasicBypassGroup is only required for UPSs
            that have a Bypass present."
    OBJECT     upsShutdownType
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one shutdown type."

    OBJECT     upsAutoRestart
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one restart type."

    OBJECT     upsConfigInputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigInputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigLowBattTime
    DESCRIPTION
            "Implementation of all possible values may be onerous
            for some systems.  Consequently, not all possible
            values must be supported.  However, at least two
            different manufacturer-selected values must be
            supported."

    ::= { upsCompliances 2 }

upsFullCompliance MODULE-COMPLIANCE
    STATUS     current
    DESCRIPTION
            "The compliance statement for UPSs that support
            advanced full-featured functions."
    MODULE -- this module
        MANDATORY-GROUPS { upsFullIdentGroup, upsFullBatteryGroup,
                  upsFullInputGroup, upsFullOutputGroup,
                  upsFullAlarmGroup, upsFullTestGroup,
                  upsFullControlGroup, upsFullConfigGroup }

    OBJECT     upsAlarmDescr
    DESCRIPTION
            "Support of all `well known' alarm types is not
            required.  The well known alarm types which must be
            supported are: upsAlarmBatteryBad, upsAlarmOnBattery,
            upsAlarmLowBattery, upsAlarmDepletedBattery,
            upsAlarmTempBad, upsAlarmInputBad, upsAlarmOnBypass,
            upsAlarmBypassBad, upsAlarmOutputOffAsRequested,
            upsAlarmUpsOffAsRequested, upsAlarmUpsOutputOff,
            upsAlarmUpsSystemOff, upsAlarmGeneralFault,
            upsAlarmDiagnosticTestFailed,
            upsAlarmCommunicationsLost, upsAlarmShutdownPending,
            and upsAlarmTestInProgress."

    OBJECT     upsTestId
    DESCRIPTION
            "Support of all `well known' test types is not
            required.  The well known test types which must be
            supported are: upsTestNoTestsInitiated,
            upsTestGeneralSystemsTest, and
            upsTestQuickBatteryTest."

    OBJECT     upsOutputSource
    SYNTAX     INTEGER {
        normal(2),
        battery(4)
    }
    DESCRIPTION
            "Support of the values other(1), none(2), bypass(4),
            booster(6) and reducer(7) is not required."

        GROUP upsFullBypassGroup
        DESCRIPTION
            "The upsFullBypassGroup is only required for UPSs that
            have a Bypass present."

    OBJECT     upsShutdownType
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one shutdown type."

    OBJECT     upsAutoRestart
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required, i.e., compliant
            systems need not support more than one restart type."

    OBJECT     upsConfigInputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigInputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputVoltage
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigOutputFreq
    MIN-ACCESS read-only
    DESCRIPTION
            "Read-write access is not required."

    OBJECT     upsConfigLowBattTime
    DESCRIPTION
            "Implementation of all possible values may be onerous
            for some systems.  Consequently, not all possible
            values must be supported.  However, at least two
            different manufacturer-selected values must be
            supported."

    ::= { upsCompliances 3 }


--
-- units of conformance
--

-- summary at a glance:

--                                      subset  basic   adv
--upsIdentManufacturer                  x       x       x
--upsIdentModel                         x       x       x

--upsIdentUPSSoftwareVersion                    x       x
--upsIdentAgentSoftwareVersion          x       x       x
--upsIdentName                          x       x       x
--upsIdentAttachedDevices               x               x
--
--upsBatteryStatus                      x       x       x  notes
--upsSecondsOnBattery                   x       x       x
--upsEstimatedMinutesRemaining                          x
--upsEstimatedChargeRemaining                           x
--upsBatteryVoltage
--upsBatteryCurrent
--upsBatteryTemperature
--
--upsInputLineBads                      x       x       x
--upsInputNumLines                              x       x
--upsInputFrequency                             x       x
--upsInputVoltage                               x       x
--upsInputCurrent
--upsInputTruePower
--
--upsOutputSource                       x       x       x  notes
--upsOutputFrequency                            x       x
--upsOutputNumLines                             x       x
--upsOutputVoltage                              x       x
--upsOutputCurrent                                      x
--upsOutputPower                                        x
--upsOutputPercentLoad                                  x
--
--
--upsBypassFrequency                            x       x  notes
--upsBypassNumLines                             x       x
--upsBypassVoltage                              x       x
--upsBypassCurrent
--upsBypassPower
--
--
--upsAlarmsPresent                      x       x       x
--upsAlarmDescr                         x       x       x  notes
--upsAlarmTime                          x       x       x
--
--upsTestId                                     x       x  notes
--upsTestSpinLock                               x       x
--upsTestResultsSummary                         x       x
--upsTestResultsDetail                          x       x
--upsTestStartTime                              x       x
--upsTestElapsedTime                            x       x
--
--upsShutdownType                       x       x       x  notes

--upsShutdownAfterDelay                 x       x       x
--upsStartupAfterDelay                          x       x
--upsRebootWithDuration                         x       x
--upsAutoRestart                        x       x       x  notes
--
--upsConfigInputVoltage                 x       x       x  notes
--upsConfigInputFreq                    x       x       x  notes
--upsConfigOutputVoltage                x       x       x  notes
--upsConfigOutputFreq                   x       x       x  notes
--upsConfigOutputVA                     x       x       x
--upsConfigOutputPower                  x       x       x
--upsConfigLowBattTime                          x       x  notes
--upsConfigAudibleStatus                        x       x
--upsConfigLowVoltageTransferPoint
--upsConfigHighVoltageTransferPoint


-- units of conformance
upsGroups             OBJECT IDENTIFIER ::= { upsConformance 2 }

upsSubsetGroups       OBJECT IDENTIFIER ::= { upsGroups 1 }

upsSubsetIdentGroup OBJECT-GROUP
    OBJECTS { upsIdentManufacturer, upsIdentModel,
              upsIdentAgentSoftwareVersion, upsIdentName,
              upsIdentAttachedDevices }
    STATUS  current
    DESCRIPTION
            "The upsSubsetIdentGroup defines objects which are
            common across all UPSs which meet subset compliance.
            Most devices which conform to the upsSubsetIdentGroup
            will provide access to these objects via a proxy
            agent.  If the proxy agent is compatible with multiple
            UPS types, configuration of the proxy agent will
            require specifying some of these values, either
            individually, or as a group (perhaps through a table
            lookup mechanism based on the UPS model number)."
    ::= { upsSubsetGroups 1 }

upsSubsetBatteryGroup OBJECT-GROUP
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
    STATUS  current
    DESCRIPTION
            "The upsSubsetBatteryGroup defines the objects that
            are common to battery groups of two-contact UPSs."
    ::= { upsSubsetGroups 2 }

upsSubsetInputGroup OBJECT-GROUP
    OBJECTS { upsInputLineBads }
    STATUS  current
    DESCRIPTION
            "The upsSubsetInputGroup defines the objects that are
            common to the Input groups of two-contact UPSs."
    ::= { upsSubsetGroups 3 }

upsSubsetOutputGroup OBJECT-GROUP
    OBJECTS { upsOutputSource }
    STATUS  current
    DESCRIPTION
            "The upsSubsetOutputGroup defines the objects that are
            common to the Output groups of two-contact UPSs."
    ::= { upsSubsetGroups 4 }


-- { upsSubsetGroups 5 } is reserved for
-- future use (upsSubsetBypassGroup)

upsSubsetAlarmGroup OBJECT-GROUP
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
    STATUS  current
    DESCRIPTION
            "The upsSubsetAlarmGroup defines the objects that are
            common to the Alarm groups of two-contact UPSs."
    ::= { upsSubsetGroups 6 }

-- { upsSubsetGroups 7 } is reserved for
-- future use (upsSubsetTestGroup)

upsSubsetControlGroup OBJECT-GROUP
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
                  upsAutoRestart }
    STATUS  current
    DESCRIPTION
            "The upsSubsetControlGroup defines the objects that
            are common to the Control groups of two-contact UPSs."
    ::= { upsSubsetGroups 8 }

upsSubsetConfigGroup OBJECT-GROUP
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
              upsConfigOutputVoltage, upsConfigOutputFreq,
              upsConfigOutputVA, upsConfigOutputPower }
    STATUS  current
    DESCRIPTION
            "The upsSubsetConfigGroup defines the objects that are
            common to the Config groups of two-contact UPSs."
    ::= { upsSubsetGroups 9 }
upsBasicGroups        OBJECT IDENTIFIER ::= { upsGroups 2 }

upsBasicIdentGroup OBJECT-GROUP
    OBJECTS { upsIdentManufacturer, upsIdentModel,
              upsIdentUPSSoftwareVersion,
              upsIdentAgentSoftwareVersion, upsIdentName }
    STATUS  current
    DESCRIPTION
            "The upsBasicIdentGroup defines objects which are
            common to the Ident group of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 1 }

upsBasicBatteryGroup OBJECT-GROUP
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery }
    STATUS  current
    DESCRIPTION
            "The upsBasicBatteryGroup defines the objects that are
            common to the battery groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 2 }

upsBasicInputGroup OBJECT-GROUP
    OBJECTS { upsInputLineBads, upsInputNumLines,
              upsInputFrequency, upsInputVoltage }
    STATUS  current
    DESCRIPTION
            "The upsBasicInputGroup defines the objects that are
            common to the Input groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 3 }

upsBasicOutputGroup OBJECT-GROUP
    OBJECTS { upsOutputSource, upsOutputFrequency,
              upsOutputNumLines, upsOutputVoltage }
    STATUS  current
    DESCRIPTION
            "The upsBasicOutputGroup defines the objects that are
            common to the Output groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 4 }

upsBasicBypassGroup OBJECT-GROUP
    OBJECTS { upsBypassFrequency, upsBypassNumLines,
              upsBypassVoltage }
    STATUS  current
    DESCRIPTION
            "The upsBasicBypassGroup defines the objects that are
            common to the Bypass groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 5 }

upsBasicAlarmGroup OBJECT-GROUP
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
    STATUS  current
    DESCRIPTION

            "The upsBasicAlarmGroup defines the objects that are
            common to the Alarm  groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 6 }

upsBasicTestGroup OBJECT-GROUP
    OBJECTS { upsTestId, upsTestSpinLock,
              upsTestResultsSummary, upsTestResultsDetail,
              upsTestStartTime, upsTestElapsedTime }
    STATUS  current
    DESCRIPTION
            "The upsBasicTestGroup defines the objects that are
            common to the Test groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 7 }

upsBasicControlGroup OBJECT-GROUP
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
              upsStartupAfterDelay, upsRebootWithDuration,
              upsAutoRestart }
    STATUS  current
    DESCRIPTION
            "The upsBasicControlGroup defines the objects that are
            common to the Control groups of compliant UPSs which
            support basic functions."
    ::= { upsBasicGroups 8 }

upsBasicConfigGroup OBJECT-GROUP
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
              upsConfigOutputVoltage, upsConfigOutputFreq,
              upsConfigOutputVA, upsConfigOutputPower,
              upsConfigLowBattTime, upsConfigAudibleStatus }
    STATUS  current
    DESCRIPTION
            "The upsBasicConfigGroup defines the objects that are
            common to the Config groups of UPSs which support
            basic functions."
    ::= { upsBasicGroups 9 }
upsFullGroups         OBJECT IDENTIFIER ::= { upsGroups 3 }

upsFullIdentGroup OBJECT-GROUP
    OBJECTS { upsIdentManufacturer, upsIdentModel,
              upsIdentUPSSoftwareVersion,
              upsIdentAgentSoftwareVersion, upsIdentName,
              upsIdentAttachedDevices }
    STATUS  current
    DESCRIPTION
            "The upsFullIdentGroup defines objects which are
            common to the Ident group of fully compliant UPSs."
    ::= { upsFullGroups 1 }

upsFullBatteryGroup OBJECT-GROUP
    OBJECTS { upsBatteryStatus, upsSecondsOnBattery,
              upsEstimatedMinutesRemaining,
              upsEstimatedChargeRemaining }
    STATUS  current
    DESCRIPTION
            "The upsFullBatteryGroup defines the objects that are
            common to the battery groups of fully compliant UPSs."
    ::= { upsFullGroups 2 }

upsFullInputGroup OBJECT-GROUP
    OBJECTS { upsInputLineBads, upsInputNumLines,
              upsInputFrequency, upsInputVoltage }
    STATUS  current
    DESCRIPTION
            "The upsFullInputGroup defines the objects that are
            common to the Input groups of fully compliant UPSs."
    ::= { upsFullGroups 3 }

upsFullOutputGroup OBJECT-GROUP
    OBJECTS { upsOutputSource, upsOutputFrequency,
              upsOutputNumLines, upsOutputVoltage,
              upsOutputCurrent, upsOutputPower,
              upsOutputPercentLoad }
    STATUS  current
    DESCRIPTION
            "The upsFullOutputGroup defines the objects that are
            common to the Output groups of fully compliant UPSs."
    ::= { upsFullGroups 4 }

upsFullBypassGroup OBJECT-GROUP
    OBJECTS { upsBypassFrequency, upsBypassNumLines,
              upsBypassVoltage }
    STATUS  current
    DESCRIPTION
            "The upsFullBypassGroup defines the objects that are
            common to the Bypass groups of fully compliant UPSs."
    ::= { upsFullGroups 5 }

upsFullAlarmGroup OBJECT-GROUP
    OBJECTS { upsAlarmsPresent, upsAlarmDescr, upsAlarmTime }
    STATUS  current
    DESCRIPTION

            "The upsFullAlarmGroup defines the objects that are
            common to the Alarm  groups of fully compliant UPSs."
    ::= { upsFullGroups 6 }

upsFullTestGroup OBJECT-GROUP
    OBJECTS { upsTestId, upsTestSpinLock,
              upsTestResultsSummary, upsTestResultsDetail,
              upsTestStartTime, upsTestElapsedTime }
    STATUS  current
    DESCRIPTION
            "The upsFullTestGroup defines the objects that are
            common to the Test groups of fully compliant UPSs."
    ::= { upsFullGroups 7 }

upsFullControlGroup OBJECT-GROUP
    OBJECTS { upsShutdownType, upsShutdownAfterDelay,
              upsStartupAfterDelay, upsRebootWithDuration,
              upsAutoRestart }
    STATUS  current
    DESCRIPTION
"The upsFullControlGroup defines the objects that are
common to the Control groups of fully compliant UPSs."
    ::= { upsFullGroups 8 }

upsFullConfigGroup OBJECT-GROUP
    OBJECTS { upsConfigInputVoltage, upsConfigInputFreq,
              upsConfigOutputVoltage, upsConfigOutputFreq,
              upsConfigOutputVA, upsConfigOutputPower,
              upsConfigLowBattTime, upsConfigAudibleStatus }
    STATUS  current
    DESCRIPTION
            "The upsFullConfigGroup defines the objects that are
            common to the Config groups of fully compliant UPSs."
    ::= { upsFullGroups 9 }

END